ELECTRIC RESISTANCE FLOOR
HEATING
Display hidden notes to specifier by using
"Tools"/"Options"/"View"/"Hidden Text".
** NOTE TO SPECIFIER ** Orbit Radiant Heating;
interior radiant heating, exterior snow melting, exterior roof and gutter ice
melting for both residential and commercial applications.
.
This section is based on the products
of Orbit Radiant Heating, which is located at:
1507 W. Park Ave.
Perkasie, PA 18944
Toll Free Tel: 800-522-3986
Tel: 215-453-9228
Fax: 215-257-7399
Email: request info
Web: www.OrbitMfg.com
[ Click Here ] for additional information.
Orbit Manufacturing has been in the
electrical heating business since 1961. We began as a manufacturer of
electrical residential and light commercial baseboard, and added an
architectural line of electrical products in 1980. In 1992, we established our
initial agreement to distribute Nexans heating cable throughout the United
States, becoming one of the first domestic radiant heating system suppliers.
Our partner, Nexans, is the worldwide
leader in the cable industry. A pioneer in electric radiant heating, Nexans has
been manufacturing radiant heating cable since 1926. Nexans' extensive
experience and superior heating cable products along with Orbit's knowledgeable
in electric radiant heating sales and customer support, form an ideal
partnership that brings you the radiant comfort that you deserve.
Residential Radiant Heating
Applications Orbit electric radiant
heating systems can be used for a wide variety of applications. For indoor
applications, our Nexans cables and mats can be used to warm any kind of floor,
including hardwood, tile, laminates and marble. For outdoor applications,
Nexans cables can melt snow and ice from ground surfaces such as concrete,
brick, pavers or asphalt, as well as roofs and gutters.
Commercial & Industrial Applications Orbit's durable electric radiant heating
systems, comprised of Nexans cables, are designed to withstand the rigors of
demanding applications in almost any commercial application, from snow and ice
melting to frost protection. Our systems can be used to melt snow and ice from
concrete, brick or asphalt, as well as from roofs and gutters.
We engineer and customize each system
to ensure you get just the right configuration for your particular application
to ensure the lowest first cost and operation expenses.
Radiant Heating Controls Orbit provides a variety of control
products for all of our electric radiant heating systems.
PART 1 GENERAL
1.1
SECTION
INCLUDES
** NOTE TO SPECIFIER ** Delete items below not required for project.
A. Electric floor heating system.
1.2
RELATED
SECTIONS
** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add
others as required.
A. Section 16050 - Basic Methods and Materials:
Power and controls wiring.
1.3
SUBMITTALS
A. Submit under provisions of Section 01300.
B. [ Product
Data ]: Manufacturer's data
sheets on each product to be used, including:
1. Preparation instructions and
recommendations.
2. Storage and handling requirements and
recommendations.
3. Installation methods.
** NOTE TO SPECIFIER ** Delete if shop drawings not required.
C. Shop Drawings:
1. Provide dimensioned layout of heater
cable as required by application.
2. Provide schematic layout of controls and
sensors.
1.4
QUALITY
ASSURANCE
A. Manufacturer Qualifications: Manufacturer shall have not less than 35
years experience manufacturing the heating cables specified in this Section.
B. Installer Qualifications: Installer shall demonstrate experience on
projects of similar size and complexity.
All wiring connections shall be done by a licensed electrician.
1.5
DELIVERY,
STORAGE, AND HANDLING
A. Store products in manufacturer's unopened
packaging until ready for installation.
1.6
PROJECT
CONDITIONS
A. Maintain environmental conditions
(temperature, humidity, and ventilation) within limits recommended by manufacturer
for optimum results. Do not install
products under environmental conditions outside manufacturer's absolute limits.
1.7
WARRANTY
A. The Electrical Contractor shall verify
and record resistance and insulation-to-ground readings of the system upon
delivery and again before start up.
B. If readings show electrical faults upon
delivery testing, then manufacturer shall replace the cable at no cost to the
Owner.
C. If readings show electrical faults
following receipt testing, then Contractor shall replace the cable at no cost
to the Owner or the manufacturer.
PART 2 PRODUCTS
2.1
MANUFACTURERS
A. Acceptable Manufacturer: Orbit Radiant
Heating, which is located at: 1507 W. Park Ave. ; Perkasie, PA 18944; Toll Free Tel: 800-522-3986; Tel:
215-453-9228; Fax: 215-257-7399; Email: sales@orbitmfg.com;
Web: www.OrbitMfg.com
** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with
requirements of Division 1 section on product options and substitutions.
B. Substitutions: Not permitted.
C. Requests for substitutions will be
considered in accordance with provisions of Section 01600.
** NOTE TO SPECIFIER ** Delete if not required.
2.2
COMMERCIAL
FLOOR HEATING SYSTEM
A. Provide a complete, integrated system,
comprised of heating cables, sensors and control panels.
1. Provide heating cables with
factory-installed cold junctions as described in this section and shown on the
Drawings.
2. Provide one Control System to operate
with a power source of:
** NOTE TO SPECIFIER ** Delete voltage not required.
a. 120 volt.
b. 208-240 volt 3 wire.
c. 277 volt 3 wire.
d. 208-240 volt 4 wire.
e. 277 volt 4 wire.
f. 460 volt.
g. 480 Volt.
** NOTE TO SPECIFIER ** Delete phase not required.
h. Single phase.
i. 3 Phase.
3. Provide Line Voltage thermostat with
temperature sensors.
4. Compliance with 2005 NEC (National
Electric Code) in 424.44:
a. Provide GFCI personal protection type
branch circuit breakers for heating cable located in normally wet areas (i.e
bathrooms, shower rooms, kitchens). Provide branch circuit protection in other
locations.
B. Heating Cables:
1. Cable shall be Series TXLP produced by
Nexans Norway A/S.
2. Provide heating cable with the following
properties:
a. Single conductor, series resistance type.
b. Twin conductor, series resistance type.
c. Tinned copper ground conductor.
d. Three layers of waterproof protection to
include:
1) Insulated by type XLPE cross-linked
polyethylene.
2) Integral full-length foil shield.
3) Surrounded with extruded PVC outer
jacket.
e. Cable shall be continuously marked with
manufacturer's name, lot number and ohms resistance per linear meter.
f. Packaged units shall be precut to
correct length with 14 gauge cold lead and patented welded splice. Field connecting of cold lead wire is not
acceptable.
g. Sized to produce a maximum of 10
Watts/lf, (maximum 30 Watts/sf.) when energized.
h. Wire insulation shall be tested and
documented before shipment with a 1000v-mega ohm meter; insulation resistance
less than 500 mega ohm shall be rejected.
i. UL listed.
j. Designed to meet current NEC regulations
when properly installed.
k. Warranty of 10 years minimum.
3. Self-regulating cable is not acceptable.
C. Temperature Control:
1. Orbit Manufacturing's CSA Approved Line
Voltage Thermostat:
2. Control of the system shall be achieved by
the use of one or more thermostats with temperature sensor as follows:
a. Model AT115-AF (Floor, Ambient, or Dual
Sensing).
3. Features:
a. CSA Approved.
b. Provide GFCI Class A 5 mA trip level for
installations of 15 Amps and under at 120/240 Volt.
c. For projects 15.1 Amps and over provide
control panel set-up and separate GFCI protection per NEC 424.44.
d. GFCI disconnect L and N (L2) using two
relays.
e. Grounded neutral detection, using 2
coils.
f. 4 event clock function.
g. Manual Mode option.
** NOTE TO SPECIFIER ** Delete standard control system if not required.
D. Control System: Standard UL Listed Orbit
RFW Series Control:
1. Enclosures shall consist of a NEMA 1
panel, designed for indoor surface or recessed mounting, including:
a. Power Control by means of Magnetic Contactors,
rated at 50 Amperes Resistive Load, Single Phase.
** NOTE TO SPECIFIER ** Delete panel type not required.
b. 50 Amp (1 Contactor) Panel.
c. 100 Amp (2 Contactor) Panel.
d. 200 Amp (4 Contactor) Panel.
e. Contactors pre-mounted and pre-wired in
the enclosure.
f. Pre-mounted and pre-wired Terminal
Connections.
** NOTE TO SPECIFIER ** Delete custom control system if not required.
E. Control System: Custom UL Listed Control
Enclosure shall consist of a NEMA 12 panel, designed for indoor surface mounting,
including:
1. Primary power disconnect switch (circuit
breaker) in accordance with NEC recommendations.
2. Power Control by means of Magnetic
Contactors, rated at 50 Amperes Resistive Load, 1 or 3 Phase, as required.
** NOTE TO SPECIFIER ** Delete contactor type not required.
a. Contactors shall be pre-mounted and
pre-wired in the enclosure.
b. Contactors shall be remotely mounted
inside NEMA rated enclosures, when NEC required GFI protection is provided by
Orbit Mfg. in lieu of the Contractor.
3. Control circuit transformer, where
required.
4. Pilots lights, indicating: Main Power On,
Each Circuit On and Control System On.
5. Touch Safe', labeled termination points
for control power, remote control connections and cable power connections.
6. The control enclosure shall bear a UL
label.
** NOTE TO SPECIFIER ** Delete if not required.
2.3
RESIDENTIAL
FLOOR HEATING SYSTEM
A. Provide a complete, integrated system,
comprised of heating cable(s), sensor(s) and control panel(s).
1. Provide heating cables with
factory-installed cold junctions as described in this section and shown on the
Drawings.
2. Provide one Control System to operate
with a power source of:
** NOTE TO SPECIFIER ** Delete voltage not required.
a. 120 Volt, Single Phase.
b. 208-240 Volt, Single Phase.
3. Provide Line Voltage thermostat with
temperature sensors.
4. Compliance with 2005 NEC (National
Electric Code) in 424.44:
a. Provide GFCI personal protection type
branch circuit breakers for heating cable located in normally wet areas (i.e
bathrooms, shower rooms, kitchens). Provide branch circuit protection in other
locations.
B. Heating Cables:
1. Cable shall be Series TXLP produced by
Nexans Norway A/S.
2. Provide heating cable with the following
properties:
a. Single conductor, series resistance type.
b. Twin conductor, series resistance type.
c. Tinned copper ground conductor.
d. Three layers of waterproof protection to
include:
1) Insulated by type XLPE cross-linked
polyethylene.
2) Integral full-length foil shield.
3) Surrounded with extruded PVC outer
jacket.
e. Cable shall be continuously marked with
manufacturer's name, lot number and ohms resistance per linear meter.
f. Packaged units shall be precut to
correct length with 14 gauge cold lead and patented welded splice. Field connecting of cold lead wire is not
acceptable.
** NOTE TO SPECIFIER ** Delete custom requirement below if not required.
g. Custom units shall be precut to correct
length with 10 gauge cold lead conductors manually crimped to the resistance
wire and tested at the factory. Field
connecting of cold lead wire is not acceptable.
h. Sized to produce a maximum of 10
Watts/lf, (maximum 30 watts/sf.) when energized.
i. Wire insulation shall be tested and
documented before shipment with a 1000v-mega ohm meter; insulation resistance
less than 500 mega ohm shall be rejected.
j. UL listed.
k. Designed to meet current NEC regulations
when properly installed.
l. Warranty of 10 years minimum.
3. Self-regulating cable is not acceptable.
C. Temperature Control:
1. Orbit Manufacturing's CSA Approved Line
Voltage Thermostat:
2. Control of the system shall be achieved
by the use of one or more thermostats with
temperature sensor as follows:
a. AT115-AF (Floor, Ambient or Dual
Sensing).
3. Features:
a. CSA Approved.
b. Provide GFCI Class A 5 mA trip level for
installations of 15 Amps and under at 120/240 Volt.
c. For projects 15.1 Amps and over provide
control panel set-up and separate GFCI protection per NEC 424.44.
d. GFCI disconnect L and N (L2) using two
relays.
e. Grounded neutral detection, using 2
coils.
f. 4 event clock function.
g. Manual Mode option.
** NOTE TO SPECIFIER ** Delete standard control system if not required.
D. Control System: Standard UL Listed Orbit
RFW Series Control:
1. Enclosures shall consist of a NEMA 1
panel, designed for indoor surface or recessed mounting, including:
a. Power Control by means of Magnetic
Contactors, rated at 50 Amperes Resistive Load, Single Phase.
** NOTE TO SPECIFIER ** Delete panel type not required.
b. 50 Amp (1 Contactor) Panel.
c. 100 Amp (2 Contactor) Panel.
d. 200 Amp (4 Contactor) Panel.
e. Contactors pre-mounted and pre-wired in
the enclosure.
f. Pre-mounted and pre-wired Terminal
Connections.
** NOTE TO SPECIFIER ** Delete custom control system if not required.
E. Control System: Custom UL Listed Control
Enclosure shall consist of a NEMA 12 panel, designed for indoor surface
mounting, including:
1. Primary power disconnect switch (circuit
breaker) in accordance with NEC recommendations.
2. Power Control by means of Magnetic
Contactors, rated at 50 Amperes Resistive Load.
** NOTE TO SPECIFIER ** Delete contactor type not required.
a. Contactors shall be pre-mounted and
pre-wired in the enclosure.
b. Contactors shall be remotely mounted
inside NEMA rated enclosures, when NEC required GFI protection is provided by
Orbit Mfg. in lieu of the Contractor.
3. Control circuit transformer, where
required.
4. Pilots lights, indicating Main Power On,
Each Circuit On and Control System On.
5. Touch Safe', labeled termination points
for control power, remote control connections and cable power connections.
6. The control enclosure shall bear a UL label.
PART 3 EXECUTION
3.1
EXAMINATION
A. Do not begin installation until
substrates/underlay have been properly prepared.
B. If substrate/underlay preparation is the
responsibility of another installer, notify Architect of unsatisfactory
preparation before proceeding.
3.2
PREPARATION
A. Coordinate installation of heating cable
with Electrical Contractor, Concrete Contractor and General Contractor.
B. Coordinate installation of heating cable
with installation of concrete framework and concrete placement.
C. Inspect the cable and controls upon
receipt of shipment, noting any damage and ensuring that the materials received
match the order and shipping documents. Compare the labels and the electrical
resistance of the heating cables with the shipping documents.
D. Ensure that electrical terminations in
the control panel(s) have not been loosened by vibration during shipment.
3.3
INSTALLATION
A. Place cables on the substrate and
position sensors as described in the manufacturer's instructions and drawings.
Perform electrical resistance testing before, during and after the finish floor
installation, per manufacturer's instructions.
B. Perform electrical installations as shown
on manufacturer's Drawings.
C. An accurate record or picture of the
cable layout for future reference.
D. Install system per manufacturer's
instructions.
3.4
INSPECTION
AND TESTING
A. Refer to manufacturer's literature for
requirements for testing, recording, and documenting resistance and
insulation-to-ground readings.
B. Take test readings before, during, and
after installation.
C. If problems are found, consult the
manufacturer.
D. If problems cannot be corrected, notify
Architect before proceeding with any overlay construction.
E. Keep testing records for inspection by
the Architect, and for subsequent submittal to the manufacturer to ensure
validation of the warranty.
3.5
PROTECTION
A. Protect installed products until
completion of project.
B. Optionally repair or preferably damaged
products before Substantial Completion.
3.6
DOCUMENTATION
AND TRAINING
A. Manufacturer shall present the Owner with
equipment start-up and operational documentation to assist in proper operation
and to maintain specified design performance.
END OF SECTION